After a minor change in operating procedure, we briefly neglected to post the results of our weekly generator tests. For completeness, here’s a list of the intervening tests…
28-08-2016 BOL1 10:12 - 10:38 Off load Passed BOL2 10:56 - 11:13 Off load Passed 05-07-2016 BOL1 10:24 - 10:42 On load Passed BOL2 10:53 - 11:16 On load Passed 12-07-2016 BOL1 10:20 - 10:49 Off load Passed BOL2 11:02 - 11:22 Off load Passed 19-07-2016 BOL1 10:15 - 10:25 Off load Passed BOL2 10:55 - 11:14 Off load Passed 28-07-2016 BOL1 10:08 - 10:32 Off load Passed BOL2 10:41 - 11:03 Off load Passed
The generator was started, then ran off-load / on-load for the durations given above, before detecting mains and shutting down in the expected timeframe.
All measured values were within their normal ranges.